3 MW Detroit MTU Generator and E-House Package

NEW ARRIVAL! Please call Dan Echino at 403-613-7134 or Larry Holman at 403-852-0966 for details and a quote.
This Generator package can be viewed at our Lloydminster, Alberta yard.  We are accepting offers so do not hesitate to submit your best offer!  Please call 1-855-5CALROC (225762) or use our contacts page if you have any questions.

3 MW Detroit MTU Generator and E-House Package

Building 1 3 MW Detroit MTU Generator

    • Medium voltage, 4160 volts, 60 Hz, 1800 RPM
    • Less than 400 hours, manufactured 2008

Originally deployed as a back-up electrical source from the decommissioned Shell Burnt Timber gas plant. Documentation and prints are available on request. This diesel unit can be configured for a dual fuel application. May be de-rated to act as primary power generation source.

Building 2 E-House with Switch Gear and MCC

  • Allan Bradley Controls with 5 KV switch gear
  • 5 KV MCCs and 480 volt MCCs included
  • 2 -1200 Amp motorized breakers
  • Allan Bradley controls permits synchronization with the grid, allowing seamless switching to generator power in the event of main service interruption. Electrical building includes HVAC, PLC , and cabinet.

Top Gear — 3MW Genset Packaqe
Generator Set Specifications
Make / Model:
0 MTU / 3000SXC6DT2 0 S/N 155538-0108 Power Rating:
0 3000kW
0 3750kVA
0 2400/4160VAC
o 3 phase
o 0.8 power factor
o

AVR 4 wire
520amps
Standby Rated
0
Basler – DECS200
Voltage Regulation:
+1—0.250/0
o Frequency Regulation:

Temperature Drift:
+/- 0.5% for a 0 to 50 degC change NCR:
0 iGARD – SIN: 29305
0 NGR2400-15-52538 0 2400V o 15amps Continuous o 160 ohms o SE-330 ground fault monitor
Engine Specification
o Make / Model:
0 MTU(Detroit Diesel)
0 SIN 528 100 708 0 MIN 20V 4000 Starter Type: 0 TDI WN TIOO-P o Air / Gas
o Start Pressure 8— 10 bar
o Air consumption Configuration: 0.7 cubic meter, per attempt
o Vee — 20 cyl. 0 4 stroke
0 16.5:1 compression ratio Horsepower:
0 4680kW Aspiration: o Twin Turbocharged, Intercooled Fuel Type:
o Diesel
Fuel Consumption (Standby):
0 100% load 212 Uhr
0 load 156 L/hr
0 load 108 L/hr Engine Fluid Capacity:
0 Oil: 390L o Coolant: 260L

Oil / Glycol Heater o Hotstart
SIN: 19075
MIN: COL1110/0602
240V, 601-lz, 1 ph, 83.25amps
Control
120V, 1.25amps
Oil Type:
0 SAE 15W40
Alternator Specifications
Make / Model
0 SIN: 20917
0 MIN: AA28179000 Voltage:
0 2400/4160\/ Hertz:
0 60Hz Design: o Brushless 0 4/6 pole o Open drip proof o Single bearing o Flexible coupling Temperature Rise:
0 105 degc / 40 degc Exciter Type: o PMG
Phase Rotation:

Alternator Cooling: o Direct drive fan (air)
Radiators
Make
Copper Core
0 SIN: 15729 0 MIN: VR80CR1049 o Date: 1 29 08
0 Customer#: 0012862C
High Temp Circuit (L.H. Side – HT 16.38 M): o Fan Motor:
Baldor Reliance
TEFC 1780 rpm
460V
3ph
60Hz
75hp o Ambient Design:
110 degF @ sea level Glycol volume:
144.2 gal (546 L)
Low Temp Circuit (R.H. Side – HT 1637 M): o Fan Motor:
Baldor Reliance
TEFC 1780 rpm
460\/
3ph
60Hz
75hp o Ambient Design:
110 degF @ sea level Glycol volume:
103 gal (390L)
Radiator Enclosure(s)
Make:
Noise Solutions Inc.
Serial #:
0 101745 & 101746
Attenuation Design Level:
0 85dBA@ 3′ / 1m
Control System
Controller:
0 MTU/DDC
0 MIN: DGC-2020
Remote HMI (SYNP-IOI): o Thomson Technology 0 Panel Type: GCS 0 SIN: W-04832 o Located in the MCC building Enclosure Rating:
0 1.P. 23
Battery Charger
SENS – Regulated Battery Charger 0 SIN: 252113 40 07
0 MIN: FCA24-10-2411U AC Input:
120VAC, 60Hz, 1 ph, 6amps o DC Output:
24VDC, IOamps
Fuel System
Day Tank:
o Make: Advanced AG & Industrial LTD.
o Year of Build: 2004
o Volume: 2273 L
o Certifications: External Tank: ULC/ORD-C142.18
o Volume: 250 bbl (39,746 L)
o Certifications: ULC
Control panel(s):
Heat tracing (external fuel lines) o Pump control (day tank supply)
Genset Enclosure
Type:
o Self-framing Building Louvers:
o Automated Building Fans:
o (2) 16″ exhaust fans
0 120VAC, 601-14 Iph.
Overhead Crane: 0 1 Ton o Manual, chain operated
Internal step-down transformer o Hammond Power Solutions 0 P/N: NMK045KB
0 120/208 -480V
0 NEMA 3R o CSA / CUL certified
Gas Detection o General Monitors 0 MIN: S4000CH Fire Detection o General Monitors
0 MIN: FL3100/FL3101
Electrical Distribution
Certification:
0 CSA
Main Breaker: 0 IOOamp, 480\/ House Power:
Internal Power Supply:
(1) 480/120-208VAC, 30kVA
(1) 120/240VAC distribution panel, 18cct
(8) dual lamp, florescent fixtures
(4) 3-way switches
(2) 120V duplex receptacles
Shipping Dimensions
Genset Building
o Length: 396″ (10,058mm)
o Width: 218″ (5,537mm)
o Height: 222″ (5,639mm)
Weight:
Diesel Day Tank Room:
o Length: 103 1/2″ (2,629mm)
o Width:
o Main Skid 87 1/4″ (2,216mm)
o Length: 396″ (10,542mm)
o Width: 218″ (5,537mm)
o Height: 1 8″ (457mm)
o Weight: 42,253 lbs (19, 166kg)
Including radiator / exhaust & rear walkway skids.
Radiator Acoustical Enclosure o Designed noise reduction o Length: o Width: o Height:
Weight:
Radiator / Exhaust Skid o Length: 183 1/4″ (4,655mm) 0 Width: 218″ (5,537mm)
Height: 18″ (457mm)
Rear walkway platform

o Length: 72″ (1 ,829mm)
o Width: 218″ (5,537mm)
o Height: 18″ (457mm)
External Fuel Tank
o Bottom Skid
Length: 10′-5″ (3,175mm)
Width: 7′-6″ (2,286mm)
Height: 10″ (254mm)
o Side Skid
Length: 20′ (6,096mm)
Width: 7′-6″ (2,286mm)
Height: 10″ (254mm)
o Double Wall Tank
Length: 21′ (6,400mm)
Diameter: 10′-0 3/8″ (3055MM)

Total Weight:
1 ,352 lbs (613kg) 
Electrical Building
5KV Switch Gear (Eaton)
Arc Flash
5 KV MCC
480 V MCC
Allen Bradley Controller
PLC Controller
Building & Distribution (Warwick)
0 480/120-208VAC, KVA 0 UPS Panel o Lighting Panel 0 HVAC
Unisorb Scrubber
NCR


Need more information?  Ready to place an order?
Please call 1-855-5CALROC (225762), use our contact page or talk to one of our sales experts directly:

Dan Echino
Cell: 403-613-7134
E-mail: dan@calroc.ca

Larry Holman
Cell: 403-852-0966
E-mail: larry@calroc.ca